Solar inverter substation SIS
Solar inverter substation SIS– is the pre-assembled substation of container-type for placing of electrical equipment – for control system, inverter, MV-transformer and distributiom devices.
Information for order of soalr inverter substation
Diagram of solar inverter substation
SIS is structurally devided into following functional parts: Details of construction
- container;
- power conversion system;
- auxiliaries.
Container is a metal sheath, which serves to assembly of electronic and electric equipment, and its protection from environmental influence.
Power convertion system – is a complex of electronic and electric equipment, which serves to power reception and conversion with voltage up to 1000 V of direct current from photovoltaic power systems in electric power of three-phase voltage 10 kV (35 kV), 50 hz of alternating current , and for delivery of generated electricity into the national network.
PCS consists of:
- ABB inverters;
- step-up transformer wth the split windinsg;
- flow-through switchgears of medium voltage.
Auxiliaries – is electronic and electric equipment, which serves to power supply of SIS-auxaliaries, and for control of additional SIS-equipment.
SIS-performance is available on the base of metal containers and monoblock concrete containers.
Functions of Solar inverter substation
Solar inverter substation implements following main functions:
- automatic generation of electric current by the prescribed algoritm;
- fulfilling of pritection and lock functions;
- synchronization to the line;
- compulsory checking of condition of main electrical equipment status and its parameters;
- process and alarm signaling in case of extraordinary situation or critical process parameters;
- access to the generating, storing and data transmissioning process about technical process tj the dispatch center screens, and printing of information in a user-friendly format;
- consumption and production records of electric power.
Structure of Solar inverter substation
Solar inverter substation consists of main equipment for energy conversion, and optional equipment for SIS auxiliaries.
Main equipment for energy conversion – inverters, transformer, medium-voltage switchgear.
Optional equipment - automatic load transfer cabinet, auxiliary power supply cabinet, microclimate system, smoke detection system, indoor lighting.
Usage conditions of Solar inverter substation
Solar inverter substation is performed in climatic version У1 defined in the standard GOST 15150, GOST 15543 and are designed to be used in following conditions:
Parameter name | Value |
Ambient air temperature | -35 °С up +45 °С |
Relative air humidity | 100% |
Height above sea level | no more than 1000 m |
Environment | Nonexplosive and nonflammable; doesn’t contain current-conducting dust, aggressive gas and vapours in concentration, which corrodes metals and insulation (atmosphere of I and II types, defined in the GOST15543.1 and 15150 standards) |
Seismic resistance defined in the standard GOST 17516.1 on MSK 64 scale | up to 8 points |
Fire safety rating | F1 |
Fire resistance rating on СНиП 21-01-97 | No more that III |
Lightning protection category | II |
Protection rating defined in the standard GOST 14254 | not less than IP33 |
Mechanical fulfillment group in the standard GOST 17516.1 | 40 |
Reliability requirements comply with | GOST 20.39.312 |
Overall dimensions of solar inverter substation
Type of container | Overall dimensions (mm) | Coverage (м2) | Weight of empty container | ||
Length | Width | Height | |||
Monoblock concrete container CK72 | 7200 | 2500 | 3550 | 18 | 24000 |
Metal container MK1 | 8200 | 2850 | 3470 | 23,37 | 6200 |
8200 | 2850 | 3470 | 23,37 | 6200 |
Monoblock concrete container SIS is a monoblock concrete construction, which is devided by diaphragms into sections. Every section has its doors and ventilating grill.
Metallic container SIS is presented by two functionally completed modules - warm and cold, which are as-installed assembly units.
Warm module SIS – inverter room with artificial system of microclimate maintenance (cooling, ventilation and heating system).
Cold module SIS – transformer cabin and Switchgear Rooms of medium voltage.
SIS has metal supporting frame, building envelopes are made of metal shaped steel with nonflammable mineral wool heat insulator.
Cooling, ventilation and heating system serves to microclimate maintenance, ventilation of transformer cabin. In rooms of high voltage units is natural ventilation used.
Modularity of SIS-container
Arrangement of equipment of substantion
Electrical parameters of solar inverter substation
№ п/п | Name of parameter | Value | |
1 | Manufacturing company of inverter | ABB | ABB |
DC side (terminating side) | |||
2 | Input voltage DC, В | 450…750 | 450…825 |
3 | Maximum input voltage DC, В | 900В (option 1000В) | 900В (option 1000В) |
4 | Critical current (Imax (DC)), А | 1145 х 2 | 1145 х 2 |
5 | Number of protected entries (in parallel), off | 40 (+/-) х 2 | 40 (+/-) х 2 |
6 | Surge protection | Class 2 | Class 2 |
7 | Connection | cablе, ring lug | cablе, ring lug |
8 | Maximal cut of connecting cable, mm2 | 185 | 185 |
9 | Screw connection size | M12 | M12 |
10 | Tightening torque, nm | 70 | 70 |
11 | Sealed input number, off | 28 | 28 |
12 | Maximal cable diameter,mm | 22 | 22 |
АС side (outgoing side) | |||
13 | Output voltage АС, кВ | 10 | 35 |
14 | Line frequency, hz | 50 | 50 |
15 | Rating capacity, kW | 1000 | 1000 |
16 | Current distortion, % | <3 | <3 |
17 | Earthing concept | TN / IT | TN / IT |
18 | Surge protection | Class 1/2 | Class 1/2 |
19 | Connection | cablе, ring lug | cablе, ring lug |
20 | Connection type | through-type | through-type |
21 | Maximal cut of connecting cable, mm2 | 300 | 300 |
22 | Screw connection size | М12/М16 | М12/М16 |
23 | Tightening torque, nm | 70 | 70 |
24 | Sealed input number, off | 6 | 6 |
25 | Maximal cable diameter,mm | 47 | 47 |
Auxiliary power supply | |||
26 | Input voltage АC, В | 380 | 380 |
27 | Line frequency | 50 | 50 |
28 | Rated input kW | 11,5 | 16,8 |
29 | Earthing concept | TN-S | TN-S |
30 | Surge protection | Class 2 | Class 2 |
31 | Connection | Cable, tubular lug | Cable, tubular lug |
32 | Maximal cut of connecting cable, mm2 | 16 | 95 |
33 | Sealed input number, off | 2 | 3 |
34 | Maximal cable diameter,mm | 22 | 33 |
SGCB-Network | |||
35 | Network type | Current loop | Current loop |
36 | Surge protection | Class 2 | Class 2 |
37 | Connection | Cable, tubular lug | Cable, tubular lug |
38 | Connection type | Star | Star |
39 | Maximal cut of connecting cable, mm2 | 1 | 1 |
40 | Sealed input number, off | 32 | 32 |
41 | Maximal cable diameter,mm | 12 | 12 |
Ethernet-Network | |||
42 | Network type | Ethernet | Ethernet |
43 | Connection | Cable | Cable |
44 | Connection type | Star, Bus | Star, Bus |
45 | Cable type | Optics | Optics |
46 | Sealed input number, off | 2 | 2 |
47 | Maximal cable diameter,mm | 12 | 12 |