SIVACON S8
Low-voltage distribution units SIVACON S8:
- Construct with closing switch
- Multi-purpose mounting construct
- Hard mounted construct (front end covers)
- Construct of hard mounted small-profiled fuses 3NJ4
- Construct of small-profiled plug-in fuses 3NJ6 / SASIL
- Reactive power compensation
Appliance
Technical characterictics
Standards and norms | Uniform tested distribution devices and combination of switching units (ТТА) |
IEC 60439-1, IEC61439-1/2, EN 60439-1 |
New IEC61439 Protection against electric-shock hazard |
DIN EN 50274 | |
Test for behavior in case of short-circuit inside the cabinet (protection against electric arc) | IEC 61641 | |
Air gaps and creepage distance |
Rated impulse withstand voltage (Uimp) Overvoltage category Pollution level |
8 kV |
Rated insulation voltage (Ui) Rated operation voltage (Uе) |
Up to 1000 V, 50/60HZ
Up to 690 V |
|
Busbar 3-роlе / 4-роlе |
Main buses
Rated current (In) Rated short-circuit withstand current к.з.(Iрк) Peak short-circuit withstand current.(Icw) |
From above/from the back |
Level of protection | Is in accordance with IEC 60529, EN 60529 | Up to IР54 (IР55*) |
Form of inner division | Is in accodance with IEC 60439-1, EN 60439-1, section 7.7 | Up to Form 4 |
Localization withstandability
Special tests in personnel protection and system are carried out according to IЕС 6164:
- Doors and end covers shouldn’t open
- Parts shoudnt break away
- There shouldn’t be holes in cover
- Detectors shouldn’t light up
- PE-conductor should be in operation
Optionally: arc-suppression barriers
Additionally: insulated busbar
Localization withstandability – pressure bleeding off
Cabinet construction
Function compartments for:
- bus
- device /
- additional equipment. Cableе/bus connection
- transverse interconnection
Identical geometrical dimensions of device units independing on:
- bus positioning
- cabinet’s depth
Cabin and housing
- Galvanized iron cabinets
- Height 2000 and 2200 mm (additionally 100 or 200mm high base)
- Powder coating of housing parts
- Angle of the door opening up to 180° (125°)
- Doors with several or one lockig device
- Doors with multipurpose hinges (hinges can be freely transfered)
- Upper cover with an explosive valve
- Level of protection IР30/31 IР40/41,IР54 (IР55)
Main busbar
- Different location of bus bar from above and from behind (from above and from below)
- Rated current up to 7010 А
- Rated peak withstand curent (Iрk) up to 330 kА
- Rated short-time withstand current Icw up to 150 kА
- Two busbars can be used in electric power distribution plants
- Unmanned bus connections
- Joints of transport units have an easy access from the front or from above
FCB –construct with automatic circuit breaker
- Fixed or drawout automatic circuit breakers for entrance, intersection and outgoing feeders
- SENTRON 3WL air circuit breakers, from 630 up to 6300 A, 3-, and 4-pole
- SENTRON 3VL compact circuit breakers, from 630 up to 1600 A, fixed
- Width of the cabinet depends on the nominal size of the circuit breaker (example: cabinet with the width of 400 mm up to In = 1600 A, 600 mm up to In = 3200 A, 1000 mm up to In = 6300 A)
- Clearly devided functional compartments
- Text and off-position when the door of the cabinet is closed
- Cable/bus connection from above, below and behind the cabinet
- Connection to busbar SIVACON 8PS,which has passed typical tests
- Separate section of auxiliary units for every circuit breaker
- Place for composite control elements and block systems
- Holder for auxiliary equipment can be disconnected and draw out from the cabinet
- Section size of cable/bus connections depends rated current of the circuit breaker
- Places of cable and busbar connections are easy to get at
- High safety for maintanance staff due to deviding into compartments
- Time for connection is remarkably reduced.
FCB - Construct with automatic circuit breaker, disconnect and outgoing, with SENTRON 3VL/3WL
BC - Construct with automatic circuit breaker – Compartment with SENTRON 3VL/3WL
РСВ/ВС – Construst with automatic circuit breaker
- Panel’s width:
Circuit breaker | Panel’s width [mm] | |||
Bus from above | Bus from behind | |||
3-polig | 4-polig | 3-polig | 4-polig | |
Cable connection | ||||
VL630 | 400 | 400 | 400 | 600 |
VL800; fixed mounted | 400 | 400 | 400 | 600 |
VL800; withdrawable | 600 | 600 | 600 | 600 |
VL1250, -1600; fixed mounted | 400 | 400 | 400 | 600 |
VL1250, -1600; withdrawable | 600 | 600 | 600 | 600 |
3WL1106, -08, - 10, -12, -16 | 400, 600 | 600 | 400, 600 | 600 |
3WL1220, -1225, -1232 | 600, 800 | 800 | 600, 800 | 800 |
3WL1340 | 800 | 1000 | 1000 | 1000 |
Bus connection | ||||
VL1600; fixed mounted | 400 | 600 | 400 | 600 |
VL1600; withdrawable | 600 | 600 | 600 | 600 |
3WL1106, -08, - 10, -12, -16 | 400, 600 | 600 | 400, 600 | 600 |
3WL1220, -1225, -1232 | 600, 800 | 800 | 600, 800 | 800 |
3WL1340, -1350, -1363 | 1000 | 1000 | 1000 | 1000 |
3WT… |
Panel’s width [mm] | |||||
Circuit breaker | BCL | BCT | |||
Bus from above | Bus from behind |
See cable connection |
|||
3-polig | 4-polig | 3-polig | 4-polig | ||
3WL1106, -08, - 10, -12, -16 | 600 | 800 | 600 | 600 | |
3WL1220, -25, -32 | 800 | 1000 | 800 | 800 | |
3WL1340 | 1000 | 1200 | 1000 | 1000 | |
3WL1350 | 1000 | 1200 | 1200 | 1200 | |
3WL1363 | 1400 | 1400 | 1400 | 1400 |
OFF – Construct of multi-purpose mounting
- Combination of different installation ways of modules
- Fixed construct with the compartment doors
- Set-in small-compartment fuse-disconnecting switches 3NJ6
- 600mm wide compartments (connection from behind)
- 1000 mm and 1200 mm wide compartments (connection from the front)
- 400mm or 600 mm wide compartment for cable connections
- Cable inlet from above, below or behind (not for3NJ6)
- Form of the inner division – up to 4b
OFFW –Construct of multi-purpose mounting – vertical busbar
- Rated current: I n up to 1620 A
- Rated short-circuit withstand current.Icw up to 65 kA*
- 3-and 4-pole
- Different ways of cable and bus connection, without drilling or perforation
- Copper profile 400 or 650 mm²
OFFW – Construct of multi-purpose mounting –Hard-mounted construct with the compartment doors
- Cable feeders
- SENTRON 3VL automatic circuit breaker
- SENTRON 3VT1…3 automatic circuit breaker
- SIRIUS 3RV automatic circuit breaker
- SENTRON 3K switch-disconnectors
- SENTRON 3NP switch-disconnectors
- Rated current In up to 630 A
- 3-and 4-pole
- Hard mounting and plugin cap (3VL)
- RCD modules (3VL)
- Manual or motor drive
- Control from the door or behind it
- Mounting panels for other equipment
OFFW – Construct of multi-purpose mounting SENTRON 3NJ6 switch-disconnector
- Adapter for installation up to 10 SENTRON 3NJ6 plug-in switch-disconnectors
- 600 mm high adapter (height of the component – 500 mm)
- SENTRON 3NJ6 switch-disconnector, In up to 630 A
- Front cable connection
OFPD Construct of small-profiled plug-in 3NJ6
- Cable feeder with
- SENTRON 3NJ6 plug-in switch-disconnector
- Mounting panels with the compartment doors
- Rated current In up to 630 A
- 1000mm or 1200 mm wide cabinet
- 400 or 600 mm wide compartment for cable connection
- up to 35 feeders on the cabinet
- Cable connection from the front, below or above
- Form of inner division up to 4b
OFPD Construct of small-profiled plug-in 3NJ6–Vertical plug-in busbar
- Rated current In up to 2180 A
- Rated short-circuit withstand current I cw up to 50 kA*
- 3- and 4-pole
- Intgrated shock-hazard protection
- Tested by touch of finger (IP20B)
- overflow orifices with 50 mm long intervals
OFF Hard-mounted construct with the front end covers
- Cable feeders with
- Rated current In up to 630 A
- 3-and 4-pole
- Permanent mounting or plug-in cap (3VL)
- Manual or motor drive
- Control through the end cover
- 1000 or 1200 mm wide cabinet
- Compartment of cable connections 400 or 600 mm
- Cable connection from the front, below, above
- Form of inner division 4b
OFF Hard-mounted construct with the front end covers – vertical buses
- Rated current: In up to 1620 A
- Rated short-circuit withstand current Icw up to 65 kA, 1 sec*
- 3-and 4-pole
- Different ways of cable or bus connections, without drilling or perforation
- Copper profile 400 or 650 mm²
OFF Hard-mounted construct with front end covers
- Single or multiple feeders
- Continuously variable holders for uniform installation
- Rotating frame for more cofortable using
- Multi-functional busbar for simple installation of built-in wiring devices
CCS – Cabinets of free design
- Width of the cabinet: 400 mm, 600 mm, 800 mm, 1000 mm and 1200 mm, (350 mm, 850 mm)*
- Inner division: Form 1, Form 2b, bus cap
- Height og the door (2000 mm or 2200 mm)
- Distributin busbar of the cabinet from behind:
- Estimated current: up to1120A
- Conventional rated short-cirquit current: up to 65kA/1s (Icc = 100kA)
- 3-and 4-pole
- DIN bus: 30 x 40 mm or 40 x 40 mm
Standard installation elements:
- Sheet metal ounting panels
- *Alpha installation sets
Cabinet with a central grounding point:
- With and without current transformers
- 200 mm extension for FCB1
or
- 600 mm or 1000 mm with cable connection
OFFD Hard mounted construct of small-profiled fuses 3NJ4
- Cable feeders with
- SENTRON 3NJ4 fused disconnecting switch
- Alpha 8GK quickly mounted sets
- Mounting panels
- Estimated current In up to 630 A
- Conventional rated short-cirquit current Icc up to 50 kA
- 3-pole
- Up to 18 feeders for one cabinet
- With and without current measurement (Small-compartment integrated current transformers)
- Total current measurement
- Form of inner division up to 2b
- 600, 800 и 1000 mm wide cabinet
- Cable connection from the front, below or above
PFC Reactive power compensation
- Capacitor units
- unrestricted up to 200 kvar
- unrestricted100 kvar
- Controller module with electronic control of reactive power for door installation
- Cluster switch with control from the door or behind it
- Width of the cabinet - 800 mm
- Up to 600 kvar, for unrestricted cabinet
- Up to 500 kvar, for restricted cabinet