SIVACON S8

Low-voltage distribution units SIVACON S8:

Appliance

shema sivaconS8 en

Technical characterictics

 technical characteristik sivaconS8 en

 

Standards and norms Uniform tested distribution devices and combination of switching units (ТТА)

IEC 60439-1,

IEC61439-1/2,

EN 60439-1

New IEC61439

Protection against electric-shock hazard

DIN EN 50274
Test for behavior in case of short-circuit inside the cabinet (protection against electric arc) IEC 61641
Air gaps and creepage distance

Rated impulse withstand voltage (Uimp)

Overvoltage category

Pollution level

8 kV
III
3

Rated insulation voltage (Ui)

Rated operation voltage (Uе)

Up to 1000 V, 50/60HZ

Up to  690 V

Busbar 3-роlе / 4-роlе

Main buses

 

Rated current (In)

Rated short-circuit withstand current к.з.(Iрк) 

Peak short-circuit withstand current.(Icw)

From above/from the back
Up to  7010 А
Up to  330 кА
Up to 150 кА, 1s

Level of protection Is in accordance with IEC 60529, EN 60529 Up to  IР54 (IР55*)
Form of inner division Is in accodance with IEC 60439-1, EN 60439-1, section 7.7 Up to  Form 4

Localization withstandability

sivaconS8 4

Special tests in personnel protection and system are carried out according to IЕС 6164: 

Optionally: arc-suppression barriers

Additionally: insulated busbar

Localization  withstandability – pressure bleeding off

sivaconS8

Cabinet construction
sivaconS8 6 1

Function compartments for:

sivaconS8 6 2Identical geometrical dimensions of device units independing on:

Cabin and housing

Main busbar
sivaconS8 8 1

 

 

sivaconS8 9

 sivaconS8 11sivaconS8 10

FCB –construct with automatic circuit breaker

sivaconS8 13

FCB -  Construct with automatic circuit breaker, disconnect and outgoing, with SENTRON 3VL/3WL

Construct with automatic circuit breaker en

BC -  Construct with automatic circuit breaker – Compartment with SENTRON 3VL/3WL

Construct with automatic circuit breaker2 en

РСВ/ВС – Construst with automatic circuit breaker

Circuit breaker Panel’s width [mm]
Bus from above Bus from behind
3-polig 4-polig 3-polig 4-polig
Cable connection
VL630 400 400 400 600
VL800; fixed mounted 400 400 400 600
VL800; withdrawable 600 600 600 600
VL1250, -1600; fixed mounted 400 400 400 600
VL1250, -1600; withdrawable 600 600 600 600
3WL1106, -08, - 10, -12, -16 400, 600 600 400, 600 600
3WL1220, -1225, -1232 600, 800 800 600, 800 800
3WL1340 800 1000 1000 1000
Bus connection
VL1600; fixed mounted 400 600 400 600
VL1600; withdrawable 600 600 600 600
3WL1106, -08, - 10, -12, -16  400, 600 600 400, 600 600
3WL1220, -1225, -1232 600, 800 800 600, 800 800
3WL1340, -1350, -1363 1000 1000 1000 1000
3WT…

Panel’s width [mm]
Circuit breaker BCL BCT
Bus from above Bus from behind

See cable

connection

3-polig 4-polig 3-polig 4-polig
3WL1106, -08, - 10, -12, -16 600 800 600 600
3WL1220, -25, -32 800 1000 800 800
3WL1340 1000 1200 1000 1000
3WL1350 1000 1200 1200 1200
3WL1363 1400 1400 1400 1400

OFF – Construct of multi-purpose mountingsivaconS8 17

 

OFFW –Construct of multi-purpose mounting – vertical busbar

sivaconS8 18

 

OFFW – Construct of multi-purpose mounting –Hard-mounted construct with the compartment doorssivaconS8 19

OFFW – Construct of multi-purpose mounting SENTRON 3NJ6 switch-disconnector

sivaconS8 20 1  sivaconS8 20 2 sivaconS8 20 3 

OFPD Construct of small-profiled plug-in 3NJ6
sivaconS8 21

OFPD Construct of small-profiled plug-in 3NJ6–Vertical plug-in busbar

OFF Hard-mounted construct with the front end covers

OFF Hard-mounted construct with the front end covers – vertical buses
sivaconS8 18

OFF Hard-mounted construct with front end covers

sivaconS8 24 2sivaconS8 24 1

CCS – Cabinets of free design
sivaconS8 25

Standard installation elements:

Cabinet with a central grounding point:sivaconS8 26 2sivaconS8 26 1

or

 

OFFD Hard mounted construct of small-profiled fuses 3NJ4

PFC Reactive power compensation
sivaconS8 28

CC Corner cabinet

sivaconS8 29 1

sivaconS8 29 2

Standards and norms